Underfloor Heating Calculator and Cost Estimate

Free calculator

Underfloor Heating Calculator: Pipe Length and Manifold Circuits

Enter the room's net area and the pipe spacing to instantly see the length of underfloor heating pipe needed and how many circuits (outlets) the manifold requires.

Underfloor Heating Calculator
Pipe length—meters
Number of circuits—circuits (≤ 75 m)
Manifold—outlets

Factor: 10 m/m² · For preliminary estimates only.

Area × factorPipe length = net area × (1 ÷ pipe spacing)
≤ 75 mMaximum length of one circuit; pipe length is divided by 75 and rounded up
Circuits = outletsThe manifold needs as many outlets as there are circuits
Net areaAreas under cabinets, fixed furniture and walls are not counted

How Is It Calculated?

The pipe is laid on the floor at equal spacing. The smaller the spacing, the more pipe per square meter and the more even the heat distribution. Pipe length per square meter is the inverse of the spacing: at 10 cm spacing, 1 ÷ 0.10 = 10 m.

Pipe spacingPipe per m²20 m² roomCircuits
10 cm10 m200 m3
12.5 cm8 m160 m3
15 cm6.7 m134 m2
20 cm5 m100 m2

The number of circuits is calculated assuming a maximum circuit length of 75 m. This tool is for preliminary estimates; a final design requires a room-by-room heat loss calculation and a circuit plan.

What Determines the Cost?

  • Total pipe length and pipe type
  • Number of manifold outlets and equipment (flow meters, valve group)
  • Insulation panels and edge strip (equal to the net area)
  • Screed, fittings and labor

For details on per-square-meter costs and system selection, see our underfloor heating cost guide.

Products for Your Calculation

Choose the manifold, pipe and fittings based on the number of circuits you calculated:

How do you adjust the flow on a manifold? Guide to adjusting a manifold with flow meters · What does a manifold with flow meters do?

Frequently Asked Questions

How do I calculate underfloor heating pipe length?

Multiply the net area by the pipe length per square meter for the chosen pipe spacing. Length per square meter is 1 ÷ pipe spacing: 10 m at 10 cm spacing, about 6.7 m at 15 cm spacing. For example, a 20 m² room needs about 200 m of pipe at 10 cm spacing.

How long should an underfloor heating circuit be?

The longer the circuit, the higher its pressure loss. Our calculator assumes a maximum circuit length of 75 m and finds the number of circuits by dividing the total pipe length by 75 and rounding up.

How many outlets does the manifold need?

Each circuit connects to one flow and one return outlet on the manifold, so the manifold needs as many outlets as there are circuits. The number of circuits in the calculator shows how many outlets you need.

Need a material list for your project?

Send us your area and floor plan, and we will work out the pipe, manifold and fittings together.

Secure Shopping

Secure payment with 256-bit SSL

Worldwide Shipping

Dispatched from Istanbul; cost calculated by destination and weight

Export Pricing

Export prices exclude Turkish VAT; commercial invoice with every order

Product Advice

Our engineers help you choose the right size and model

Hello! 👋
Send us your questions and quote requests on WhatsApp.
ideasoft e-ticaret paketleri ile hazırlandı.